Typical Project Configuration · Customizable Range · 600kW

600 kW Weichai Open Diesel Generator

This 600 kW open generator serves medium-to-large factories, campuses and expansion projects. The alternator, controller, voltage and tank can be configured for motor starting, duty and local service conditions.

600 kWWeichai engineAlternator selectableProject configuration

Product photos · Typical configuration

Configuration overview

Reference 600 kW Weichai open-generator configuration for factories, commercial facilities and expansion loads, covering key parameters, alternator, controls and acceptance boundaries.

Reference output
600 kW / 750 kVA @ PF 0.8
Package format
Open package for a compliant generator room
Engine platform
Weichai
Alternator
Project-selected alternator
Frequency and speed
50Hz / 1500rpm · 60Hz / 1800rpm
Electrical output
Three-phase, four-wire · Project voltage

This page presents one typical project configuration to explain output, brand combination, package format and system interfaces. The same range covers additional outputs and options; the final engine model, rating, voltage, controller, tank, dimensions and supply scope are defined for the project.

Applications

Recommended applications and package choice

Recommended for

Fits projects with defined loads and a need to balance cost and serviceability

For production auxiliaries, pumps, chillers and commercial backup, the alternator and control package can be selected against load steps, local support and lead time.

Consider another package

A 600 kW load sum does not replace a motor-starting study

Large motors, VFDs, UPS systems and nonlinear loads may require more transient capability, PMG excitation or staged loading before quotation.

Typical application
Factory expansion and production auxiliaries
Typical application
Campus and large commercial backup
Typical application
Pumps, chillers and other motor loads

Core configuration

Four core configurations behind reliable operation

01

Engine and cooling

The engine and radiator are matched to output, duty and ambient temperature, with attention to load response, service access and local support.

02

Alternator

The alternator is selected for load characteristics, excitation, insulation and temperature rise; PMG can be specified for demanding motors or UPS loads.

03

Controls and protection

The controller can integrate ATS, paralleling and remote communications together with breaker, emergency stop, charging and protection functions.

04

Structure and interfaces

The base, mounts, grounding, cable exit and lifting interfaces form the package structure; container versions also integrate airflow, exhaust, weatherproof doors and service space.

Key parameters

Parameters used for project selection

These are the parameters that shape selection and interfaces. Fuel consumption, noise and dimensions are supplied after the engine model, load factor and site environment are defined.

Reference output600 kW / 750 kVA @ PF 0.8
Rating basisPrime/standby rating confirmed against the final engine model, ISO 8528 conditions and project duty
Frequency / speed50 Hz / 1500 rpm or 60 Hz / 1800 rpm
Rated voltage380 / 400 / 415 / 440 / 480 V; other voltages by project
Phase / power factorThree-phase, four-wire; reference PF 0.8
Control systemDSE / ComAp / SmartGen selected for ATS, paralleling and communications
Cooling and environmentMatched radiator; 40°C or 50°C ambient capability verified by model
Fuel autonomyBase tank, day tank or bulk storage sized from target runtime and usable fuel volume

Quality and delivery

Delivery evidence from components and structure to testing

01

Nameplates and BOM

Engine, alternator, controller and breaker brands, models and serial information are listed in the technical and delivery documents.

02

Structure and workmanship

Base steel, welds, fasteners, mounts and coating are included in manufacturing inspection; container packages also cover doors, hinges, locks, seals and lifting points.

03

Cooling and electrical

Radiator, airflow, wiring terminations, grounding, protection and safety separation support loaded stability and long-term serviceability.

04

Factory-test records

Factory records can cover starting, no-load and staged-load operation, voltage, frequency, alarms and protection, with witnessed FAT available by project.

Project configuration

Optional systems and project inputs

Optional systems

  • ATS transfer and low-voltage distribution
  • Paralleling, N+1 and future expansion
  • Base tank, day tank and automatic transfer
  • Remote monitoring, communications and records
  • Breaker, charger, heaters and spares package
  • Special voltage, hot/high-altitude and corrosion protection

Information needed for an accurate proposal

  • Critical-load list, maximum simultaneous load and starting sequence
  • Prime/standby duty and expected annual operating hours
  • Country, frequency, voltage, grounding and grid boundary
  • Temperature, altitude, dust, salt exposure and noise target
  • Fuel runtime, refueling route and fire requirements
  • Transport, lifting, foundation, installation and FAT/SAT responsibility

Ask an engineer to verify this package against the real loads

Provide the country and city, load list, frequency, voltage, duty, installation environment and required delivery. A HOHANK engineer will verify output, component selection, interfaces and the supply boundary.